Baumert has developed a wide range of fire-resistant doors to protect sensitive sites against fire regardless of its origin.
The fire performance of a door or door block is defined by its ability to withstand fire for a specified period of time. The result is fire ratings obtained during tests carried out by approved laboratories according to standardized protocols.
It is the ability of a building element with a compartmentalization function to withstand exposure to fire on one side only without transmission to the unexposed side due to the passage of significant quantities of flames or hot gases from the fire to the unexposed side.
They can cause either the surface not exposed to the fire to be ignited or of a material adjacent to this surface.
Radiation limitation is the ability of a building element - when exposed to fire, on one side only - to reduce the spread of fire due to radiation, either through the element or from the side not exposed to surrounding materials.
The main objective of an EW classified door is to guarantee the impermeability to flames from the burnt room to the protected room and to minimize the effects of radiation (Radiation < 15 kW/m²).
| Flux (kW/m²)  | Conséquences | 
|---|---|
| 240 | Rayonnement d'un feu intense (1150°C) | 
| 150 | Rayonnement d'un feu moyen (1000°C) | 
| 100 | Témpérature de 100°C dans 10 cm de beton pendant 3 heures | 
| 27 | Ignition spontanée du bois en 40 s | 
| 5 | Flux minimal létal en 60 s | 
| 2,9 | Flux minimal létal en 120 s | 
| 1 | Rayonnement solaire en zone équatoriale | 
It is the ability of the building element to withstand exposure to fire on one side only without transmitting it as a result of significant heat transfer from the exposed side to the unexposed side. Transmission must be limited so as not to ignite the unexposed surface or any material in its immediate vicinity (always used in addition to an E classification).
In the particular case of door blocks, one of the following two options for thermal insulation criteria must be used:

Performance is expressed in minutes. Thus, a door classified as EI 60 is a fire door that remains stable in a fire for at least one hour.
| E Integrity  | EW Fire resistant and limited radiation  | EI2 Integrity  and insulation  | EI1 Integrity  and insulation  | 
|---|---|---|---|
| E 15 | EW 15 | EI2 15  | EI1 15  | 
| E 30 | EW 30 | EI2 30  | EI1 30  | 
| E 45 | EW 45 | EI2 45  | EI1 45  | 
| E60 | EW 60 | EI2 60  | EI1 60  | 
| E 90 | EW 90 | EI2 90  | EI1 90  | 
| E 120 | EW 120 | EI2 120  | EI1 120  | 
| E 180 | EW 180 | EI2 180  | EI1 180  | 
| E 240 | EW 240 | EI2 240  | EI1 240  | 
Fire prevention is based on a combination of best practices, compliance with standards and the use of appropriate equipment, such as fire doors. The installation of doors that comply with current standards is essential to limit the spread of flames and ensure the safety of sensitive sites. Baumert has a wide range of doors but also fire-resistant partitions and to the flames as well as multi-required technical doors to secure your critical infrastructures against natural, biological or terrorist risks.




.jpeg)


.jpeg)
.jpeg)
